Industrial/Commercial/Residential
Generator Sets
Models:
20--2800 kW
TP-5700 7/93d
Installation
Vista de página 0
1 2 3 4 5 6 ... 55 56

Resumo do Conteúdo

Página 1 - Installation

Industrial/Commercial/ResidentialGenerator SetsModels:20--2800 kWTP-5700 7/93dInstallation

Página 2 - California Proposition 6 5

TP-5700 7/93VI Safety Precautions and InstructionsNoticeNOTICEThis generator set has beenrewired from its nameplate voltageto246242NOTICEVoltage recon

Página 3 - Table of Contents

TP-5700 7/93 iIntroductionIntroductionThis manual provides installation instructions for20--2800 kW generator sets. Operation manuals andwiring diagra

Página 5 - Accidental Starting

TP-5700 7/93 1Section 1 GeneralSection 1 GeneralIndustrial power systems give years of dependableservice if installed using the guidelines provided in

Página 6 - Fuel System

TP-5700 7/932 Section 1 GeneralTP-5700-11. Exhaust thimble (for wall or ceiling)2. Silencer3. Supports4. Flexible sections5. Duct work for cooling air

Página 7 - Electrical Shock

TP-5700 7/93 3Section 2 Load and TransportSection 2 Load and TransportTo ensure personal safety while preventing damage tothe product, we strongly rec

Página 8

TP-5700 7/934 Section 2 Load and TransportD A four-point lifting method is necessary to lift thegenerator set. To maintain generator balance duringlif

Página 9 - Moving Parts

TP-5700 7/93 5Section 2 Load and TransportD Do not attach lifting hooks to outside reinforcingplate on skid. Attach lifting hooks to skid exactly assh

Página 10

TP-5700 7/936 Section 2 Load and TransportNotes

Página 11 - Service Assistance

TP-5700 7/93 7Section 3 LocationSection 3 Location3.1 Location FactorsLocation is the key to a proper installation. The followingsections will deal wi

Página 12

Engine exhaust from this product contains chemicalsknown to the State of California to cause cancer, birthdefects, or other reproductive harm.WARNINGC

Página 13 - Section 1 General

TP-5700 7/938 Section 3 Location3.3 MountingTypical mounting surface details and dimensions areshown in Figure 3-1. The recommended mountingsurface is

Página 14 - TP-5700-1

TP-5700 7/93 9Section 3 LocationThe composition of the mounting pad should followstandard practice for the required loading. Commonspecifications call

Página 15 - Section 2 Load and Transport

TP-5700 7/9310 Section 3 LocationNotes

Página 16 - 1. Lifting fixture

TP-5700 7/93 11Section 4 Air RequirementsSection 4 Air Requirements4.1 GeneralAn ample flow of clean, cool air is required to supportcombustion and di

Página 17 - 2.1.3 Subbase Fuel Tank

TP-5700 7/9312 Section 4 Air RequirementsIn many installations it may be desirable to installlouvers in the inlet and outlet openings. Louvers may bee

Página 18

TP-5700 7/93 13Section 4 Air Requirements4.3 Forced AirWith the forced-air system, cooling air is drawn inthrough the front of the engine, circulated

Página 19 - Section 3 Location

TP-5700 7/9314 Section 4 Air Requirements4.4 Air-Vac Cooling SystemThe air flow direction with the Air-Vac system is theopposite of the conventional

Página 20 - 3.3 Mounting

TP-5700 7/93 15Section 4 Air Requirements4.5 Air VentThe air vent system is used on some air-cooled gas andhas been used on some diesel models. It inc

Página 21 - 3.4 Vibration Isolation

TP-5700 7/9316 Section 4 Air Requirements4.6 Liquid-Cooled ModelsThe three most common liquid cooling systems used forgenerator sets are unit-mounted

Página 22

TP-5700 7/93 17Section 4 Air RequirementsThe connection from the radiator duct flange to theductwork should be heavy canvas, silicone or similarflexib

Página 23 - Section 4 Air Requirements

Table of ContentsTP-5700 7/93 Table of ContentsProduct Identification Information Inside front cover...Safety

Página 24 - 4.2 Air-Cooled Generators

TP-5700 7/9318 Section 4 Air RequirementsThe engine water pump can be used to circulate waterthrough the remote radiator providing that the verticaldi

Página 25 - 4.3 Forced Air

TP-5700 7/93 19Section 4 Air Requirements71234651. Ventilation fan (for heat rejected from exhaust and engine)2. City water in3. Flexible section4. Ma

Página 26 - 4.4 Air-Vac Cooling System

TP-5700 7/9320 Section 4 Air Requirements4.11 Block HeatersBlock heaters are recommended on all standbyapplications where the generator is subject tot

Página 27 - 4.5 Air Vent

TP-5700 7/93 21Section 5 Exhaust SystemSection 5 Exhaust SystemProper installation of the exhaust system is essential toobtain satisfactory performanc

Página 28 - 4.6 Liquid-Cooled Models

TP-5700 7/9322 Section 5 Exhaust System5.1 Flexible SectionA section of flexible exhaust line should be installedwithin 2 feet (51 mm) of the engine e

Página 29 - 4.8 Remote Radiator Cooling

TP-5700 7/93 23Section 5 Exhaust System5.4 Double-Sleeve ThimblesIf the exhaust pipe should need to pass through a wall orroof, an exhaust thimble mus

Página 30 - 4.10 Cooling Tower

TP-5700 7/9324 Section 5 Exhaust SystemNotes

Página 31

TP-5700 7/93 25Section 6 Fuel SystemsSection 6 Fuel SystemsWhen planning an installation, check state and localregulations regarding fuel storage and

Página 32 - 4.12 Recommended Coolant

TP-5700 7/9326 Section 6 Fuel Systems1234TP-5700-61. Generator set skid2. Side view3. Subbase fuel tank4. End viewFigure 6-2 Subbase Fuel Tank6.2 Main

Página 33 - Section 5 Exhaust System

TP-5700 7/93 27Section 6 Fuel SystemsFlexible connections must be used wherever there maybe relative motion between piping and suppliedequipment. Alwa

Página 34 - 5.3 Piping

Table of Contents, continuedTP-5700 7/93Table of ContentsSection 7 Electrical Requirements 35...

Página 35 - 5.4 Double-Sleeve Thimbles

TP-5700 7/9328 Section 6 Fuel Systems6.5 Auxiliary Fuel PumpsEngine-driven fuel transfer pumps usually develop amaximum of 7 psi (48 kPa) pressure and

Página 36

TP-5700 7/93 29Section 6 Fuel Systems6.6 Gasoline Fuel SystemsDue to code restrictions which do not allow storage ofmore than one gallon (3.8 L) of ga

Página 37 - Section 6 Fuel Systems

TP-5700 7/9330 Section 6 Fuel Systems6.7 Natural or LP Gas FuelSystemsNatural and LP (liquified petroleum) gas fuel systemsshould be designed and inst

Página 38 - 6.3 Fuel Lines

TP-5700 7/93 31Section 6 Fuel Systems1 2 35TP-5700-649108761. Carburetor2. Load adjustment valve3. Converter (vaporizer)4. Solenoid valve5. LP gas fil

Página 39 - 6.4 Transfer Tanks

TP-5700 7/9332 Section 6 Fuel Systems6.8 Flexible ConnectorAn approved flexible connector should always be usedbetween stationary gas piping and the e

Página 40 - 6.5 Auxiliary Fuel Pumps

TP-5700 7/93 33Section 6 Fuel Systems6.11 LP Gas Fuel CharacteristicsLP gas is supplied as a liquid in pressure tanks. It iseasily adaptable to statio

Página 41 - 6.6 Gasoline Fuel Systems

TP-5700 7/9334 Section 6 Fuel Systems6.15 Natural GasNatural gas is in a vapor state as supplied from the utility.This fuel system, therefore, consist

Página 42 - 6.7 Natural or LP Gas Fuel

TP-5700 7/93 35Section 7 Electrical RequirementsSection 7 Electrical RequirementsBefore installing the generator set, provide for electricalconnection

Página 43 - TP-5700-6

TP-5700 7/9336 Section 7 Electrical Requirements7.2 Electrical ConnectionsSeveral electrical connections must be made betweenthe generator set and oth

Página 44 - 6.10 Fuel Regulators

TP-5700 7/93 37Section 7 Electrical Requirements7.4 Terminal Connector TorqueUse the torque values shown in Figure 7-4 or Figure 7-5for terminal conne

Página 45 - (Natural and LP Gas)

TP-5700 7/93 ISafety Precautions and InstructionsSafety Precautions and InstructionsIMPORTANT SAFETY INSTRUCTIONS.Electromechanical equipment,includin

Página 46 - 6.16 Combination Gas-Gasoline

TP-5700 7/9338 Section 7 Electrical Requirements7.5 Automatic Transfer SwitchesA typical standby system has at least one automatictransfer switch conn

Página 47 - 7.1 Batteries

TP-5700 7/93 39Section 7 Electrical Requirements7.9 Remote Emergency StopSwitchThe emergency stop switch allows immediate shutdownof the generator fro

Página 48 - 7.3 Load Lead Connections

TP-5700 7/9340Section 7 Electrical RequirementsTP-5700 7/93GENERATOR JUNCTION BOXSAFEGUARDCIRCUIT BREAKERTERMINAL STRIP(IN JUNCTION BOX)RUN RELAYKITBA

Página 49 - 7.4 Terminal Connector Torque

TP-5700 7/93 Appendix A-1Appendix A AbbreviationsThe following list contains abbreviations that may appear in this publication.A, amp ampereABDC after

Página 50 - Front View Side View

TP-5700 7/93A-2 Appendixkg kilogramkg/cm2kilograms per squarecentimeterkgm kilogram-meterkg/m3kilograms per cubic meterkHz kilohertzkJ kilojoulekm kil

Página 52 - GENERATOR JUNCTION BOX

E 1993, 2001, 2003 by Kohler Co. All rights reserved.TP-5700 7/93dKOHLER CO. Kohler, Wisconsin 53044Phone 920-565-3381, Web site www.kohlergenerators.

Página 53 - Appendix A Abbreviations

TP-5700 7/93II Safety Precautions and InstructionsBattery short circuits. Explosioncan cause severe injury or death.Short circuits can cause bodily in

Página 54

TP-5700 7/93 IIISafety Precautions and InstructionsThe fuel system. Explosive fuelvapors can cause severe injury ordeath. Vaporized fuels are highlyex

Página 55

TP-5700 7/93IV Safety Precautions and InstructionsHazardous voltage.Backfeed to the utility system cancause property damage, severeinjury, or death.If

Página 56 - TP-5700 7/93d

TP-5700 7/93 VSafety Precautions and InstructionsServicing the transfer switchcontrols and accessories within theenclosure. Hazardous voltage cancause